DGH D5300M MODBUS Analog Thermocouple Input Module

  • DGH

Product Features

  • 8 conversions per second
  • Accuracy: ±1°C
  • Resolution: 1°C
  • Common mode rejection: 100dB at 50/60Hz
  • Autozero and Autocalibration
  • Input burnout protection to 250Vac
  • Temperature range of -25°C to +70°C

Applications

  • Non-compliant


The D5300M thermocouple input module is part of the DGH’s D5000M low cost multichannel MODBUS data acquisition module family. This module features four channels, each accepting input signal from the choice of four thermocouple types (J, K, T and E). The module converts the thermocouple signal to digital data at the rate of 8 conversions per second, then converts the data to engineering units using the lookup tables, storing the latest data in the buffer. The data can be retrieved by sending an appropriate command from the host computer. For extra security, it utilises a non-volatile EEPROM (Electrically Erasable Programmable Read Only Memory) to store all user-selectable settings, meaning the values are maintained in the event of power loss. The D5300M comes pre-set with default values of 300 baud, one start bit, eight data bits, one stop bit, no parity and any address recognized, but these values can be easily changed by the user. The modules are designed to be compatible with all popular computers utilising RS-232 or RS-485 port and no software is necessary to start using them, although the utility software is provided. The D5300M can be mounted on a DIN-rail if required (MK-1 mounting kit required) and can be combined with other D5000 series modules to build a low cost data logger or a data acquisition system for given application.

  • 4 channel analog-to-digital thermocouple input module
  • Choice of RS-232 or RS-485 output
  • Choice of thermocouple type input: J (-200°C to +760°C), K (-150°C to +1250°C), T (-200°C to +400°C) or E (-100°C to +1000°C)
  • Communicates using DGH ASCII or MODBUS RTU protocol
  • User-selectable features include °C or °F, analog input range, baud rate, parity type and others
  • Overall accuracy (error from all sources, at 0-40°C ambient): ±1°C
  • Resolution: ±1°C
  • Lead resistance effect: <20µV per 350Ω
  • Open Thermocouple indication
  • Automatic cold junction compensation and linearisation
  • RS-232 versions are limited to one ADC per serial port (due to MODBUS RTU not supporting echoing)
  • Power requirements: Serial = 0.75W
  • Temperature range -25°C to +70°C

The applications for the D5300M data acquisition modules include:

  • Process monitoring and control
  • Remote data logging to any host computer
  • Product testing
  • Direct connection to modems

Specifications

Weight 0.00000 kg
Dimensions 27.94 x 62.23 x 91.44mm
Input/Output

4 Analog Inputs, 4 Digital Outputs

Number of Channels

4 Channels

Output

RS-232, RS-485

Power Requirements

Unregulated +10V to +30Vdc Serial 0.75W maximum

Series / Model

,

Thermocouple Type

E (-100 to +1000°C), J (-200 to +760°C), K (-150 to +1250°C), T (-200 to +400°C)

DGH D5000M Technical Library

We are pleased to provide you with a range of additional content including videos, product datasheets, case studies, white papers and application notes for your reference. Please see below for the latest content available:

 

 

DOCUMENTATION
DGH D5000M Series Datasheet
DGH D5000M Series User Manual
Command set for D5000M Series
Register map for D5000M series

Related Products

  • DGH

DGH D5300M MODBUS Analog Thermocouple Input Module