DGH D5100M MODBUS Analog Voltage Input Module Series

Product Features

  • 8 conversions per second
  • Accuracy: ±0.02% of FS maximum
  • Resolution: 0.01% of FS (4 digits)
  • Common mode rejection: 100dB at 50/60Hz
  • Input impedance of ≤±1V input =100MΩ minimum and ≥±5V input =1MΩ minimum
  • Temperature range of -25°C to +70°C
  • Non-compliant

The D5100M voltage input module is part of the DGH’s D5000M low cost multichannel MODBUS data acquisition module family. This module features four channels, each accepting voltage input signal from the choice of five different voltage ranges (±100mV, ±1V, ±5V, ±10V and ±100V) and continuously converts the data at the rate of 8 conversions per second, then converts the digital data to engineering units using the lookup tables, storing the latest data in the buffer. The data can be retrieved by sending a command from the host computer. For extra security, it utilises a non-volatile EEPROM (Electrically Erasable Programmable Read Only Memory) to store all user-selectable settings, meaning the values are maintained in the event of power loss. The D5100M comes pre-set with default values of 300 baud, one start bit, eight data bits, one stop bit, no parity and any address recognized, but these values can be easily changed by the user. The modules are designed to be compatible with all popular computers utilising RS-232 or RS-485 port and no software is necessary to start using them, although the utility software is provided. The D5100M can be mounted on a DIN-rail if required (MK-1 mounting kit required) and can be combined with other D5000M series modules to build a low cost data logger or a data acquisition system for given application.

  • Four-channel analog-to-digital voltage input module
  • Choice of RS-232 or RS-485 output
  • Choice of 5 different ranges: ±100mV, ±1V, ±5V, ±10V and ±100V
  • Communicates using DGH ASCII or MODBUS RTU protocol
  • User-selectable features include analog input range, baud rate, parity type and others
  • Accuracy: +/-0.02% of full scale
  • Resolution: 0.01% of full scale
  • Span temperature coefficient: ±50ppm/°C maximum
  • Input burnout protection to 250 Vac
  • Input impedance: ≤±1V input =100MΩ minimum and ≥±5V input =1MΩ minimum
  • RS-232 versions are limited to one ADC per serial port (due to MODBUS RTU not supporting echoing)
  • Power requirements: Serial = 0.75W
  • Temperature range -25°C to +70°C

The applications for the D5100M data acquisition modules include:

  • Process monitoring and control
  • Remote data logging to any host computer
  • Product testing
  • Direct connection to modems

Specifications

Weight 0.00000 kg
Dimensions 27.94 x 62.23 x 91.44mm
Input

±100mV, ±1V, ±5V, ±10V, ±100V

Input/Output

4 Analog Inputs, 4 Digital Outputs

Number of Channels

4 Channels

Output

RS-232, RS-485

Power Requirements

Unregulated +10V to +30Vdc Serial 0.75W maximum

Series / Model

,

Product Variations

SKUInputOutput 
DGH D5100M MODBUS Analog Voltage Input Module Series±100mVRS-232

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±100mVRS-485

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±100VRS-232

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±100VRS-485

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±10VRS-232

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±10VRS-485

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±1VRS-232

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±1VRS-485

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±5VRS-232

Request Quote

DGH D5100M MODBUS Analog Voltage Input Module Series±5VRS-485

Request Quote

  • DGH

DGH D5100M MODBUS Analog Voltage Input Module Series