DGH D3100 Voltage Output Module

Product Features

  • 12-bit DAC, 1000 conversions per second
  • Accuracy: ±0.1% of FS maximum
  • Zero drift ±30µV/°C
  • Output Isolation of 500V rms
  • Settling time to 0.1% of FS: 300µs typical, 1ms maximum
  • Voltage levels of ±30V without damage
  • Temperature range of -25°C to +70°C
  • Non-compliant

The D3100 voltage output module is part of the DGH’s data acquisition module family. This output module converts digital ASCII signal from a host computer, received via RS-232 or RS-485 ports, to analog DC voltage output at the rate of 1000 conversions per second. Six output signal choices are supported (±1V, ±5V, ±10V, ±0-1V, ±0-5V and ±0-10V). The signals can then be used to control annunciators, acutators or other hardware. The D3100 module is a cost-effective model, ideal for simple step function control applications. These modules utilise a non-volatile EEPROM (Electrically Erasable Programmable Read Only Memory) to store all user-selectable settings, meaning the values are maintained in the event of power loss. The D3100 comes pre-set with default values of 300 baud, one start bit, eight data bits, one stop bit, no parity and any address recognized, but these values can be changed by the user. The modules are designed to be compatible with all popular computers utilising RS-232C or RS-485 ports and no software is necessary to start using them, although the utility software is provided. The D3100 can be mounted on a DIN-rail if required (MK-1 mounting kit required) and can be combined with other DGH modules to provide complete customised data acquisition system for given application.

  • Computer-to-analog voltage output module
  • Choice of RS-232 or RS-485 Input
  • Choice of 6 different outputs: ±1V, ±5V, ±10V, 0-1V, 0-5V and 0-10V
  • Communicates using ASCII protocol
  • User-selectable features include analog input range, baud rate, parity type and others
  • Accuracy: ±0.1% of full scale range maximum
  • 12-bit output resolution
  • Span temperature coefficient: ±50ppm/°C maximum
  • 1000 conversions per second
  • Settling time: 300µs typical (1ms maximum)
  • Power requirements: Serial = 0.75W
  • Temperature range -25°C to +70°C

The applications for the D3100 data acquisition modules include:

  • Motion control
  • Motor speed control
  • Robotic welding control
  • Interfaces to modems
  • Programmable analog source for product test

Specifications

Weight 0.00000 kg
Dimensions 27.94 x 62.23 x 91.44mm
Input

RS-232C, RS-485

Input/Output

1 Analog Output, 3 Digital Inputs

Number of Channels

1 Channel

Output

±1V, ±5V, ±10V, 0 to 1V, 0 to 5V, 0 to 10V

Power Requirements

Unregulated +10V to +30Vdc Serial 0.75W maximum

Series / Model

,

SKUInputOutput 
DGH D3100 Voltage Output ModuleRS-232C±10V

Request Quote

DGH D3100 Voltage Output ModuleRS-485±10V

Request Quote

DGH D3100 Voltage Output ModuleRS-232C±1V

Request Quote

DGH D3100 Voltage Output ModuleRS-485±1V

Request Quote

DGH D3100 Voltage Output ModuleRS-232C±5V

Request Quote

DGH D3100 Voltage Output ModuleRS-485±5V

Request Quote

DGH D3100 Voltage Output ModuleRS-232C0 to 10V

Request Quote

DGH D3100 Voltage Output ModuleRS-4850 to 10V

Request Quote

DGH D3100 Voltage Output ModuleRS-232C0 to 1V

Request Quote

DGH D3100 Voltage Output ModuleRS-4850 to 1V

Request Quote

DGH D3100 Voltage Output ModuleRS-232C0 to 5V

Request Quote

DGH D3100 Voltage Output ModuleRS-4850 to 5V

Request Quote

Related Products

  • DGH

DGH D3100 Voltage Output Module